= 18. CHAPTER 18 — EARTHQUAKE-RESISTANT STRUCTURES | |
= 18.7 — Columns of special moment frames | |
== 18.7.1 Scope | |
=== 18.7.1.1 This section shall apply to columns of special | |
moment frames that form part of the seismic-force-resisting | |
system and are proportioned primarily to resist flexure, | |
shear, and axial forces. | |
== 18.7.2 Dimensional limits | |
=== 18.7.2.1 Columns shall satisfy (a) and (b): | |
(a) The shortest cross-sectional dimension, measured on a | |
straight line passing through the geometric centroid, shall | |
be at least 300 mm; | |
(b) The ratio of the shortest cross-sectional dimension to | |
the perpendicular dimension shall be at least 0.4. | |
== 18.7.3 Minimum flexural strength of columns | |
=== 18.7.3.1 Columns shall satisfy 18.7.3.2 or 18.7.3.3, except | |
at connections where the column is discontinuous above the | |
connection and the column factored axial compressive force | |
Pu under load combinations including earthquake effect, E, | |
are less than Ag fc′/10. | |
=== 18.7.3.2 The flexural strengths of the columns shall satisfy | |
ΣMnc ≥ (6/5)ΣMnb (18.7.3.2) | |
ΣMnc is sum of nominal flexural strengths of columns | |
framing into the joint, evaluated at the faces of the joint. | |
Column flexural strength shall be calculated for the factored | |
axial force, consistent with the direction of the lateral forces | |
considered, resulting in the lowest flexural strength. | |
ΣMnb is sum of nominal flexural strengths of the beams | |
framing into the joint, evaluated at the faces of the joint. | |
In T-beam construction, where the slab is in tension under | |
moments at the face of the joint, slab reinforcement within | |
an effective slab width defined in accordance with 6.3.2 shall | |
be assumed to contribute to Mnb if the slab reinforcement is | |
developed at the critical section for flexure. | |
Flexural strengths shall be summed such that the column | |
moments oppose the beam moments. Equation (18.7.3.2) | |
shall be satisfied for beam moments acting in both directions | |
in the vertical plane of the frame considered. | |
=== 18.7.3.3 If 18.7.3.2 is not satisfied at a joint, the lateral | |
strength and stiffness of the columns framing into that joint | |
shall be ignored when calculating strength and stiffness of | |
the structure. These columns shall conform to 18.14. | |
= R18.7 — Columns of special moment frames | |
== R18.7.1 Scope | |
This section applies to columns of special moment frames | |
regardless of the magnitude of axial force. Before 2014, the | |
Code permitted columns with low levels of axial stress to be | |
detailed as beams. | |
== R18.7.2 Dimensional limits | |
The geometric constraints in this provision follow from | |
previous practice (Seismology Committee of SEAOC 1996). | |
== R18.7.3 Minimum flexural strength of columns | |
The intent of 18.7.3.2 is to reduce the likelihood of yielding | |
in columns that are considered as part of the seismic-forceresisting | |
system. If columns are not stronger than beams | |
framing into a joint, there is increased likelihood of inelastic ... | |
American Concrete Institute – Copyrighted © Material – www.concrete.org | |
PART 5: EARTHQUAKE RESISTANCE 305 | |
18 Seismic | |
No further reproduction or distribution is permitted. | |
== R18.7.3 Continuation | |
action. In the worst case of weak columns, flexural yielding | |
can occur at both ends of all columns in a given story, | |
resulting in a column failure mechanism that can lead to | |
collapse. Connections with discontinuous columns above the | |
connection, such as roof-level connections, are exempted if | |
the column axial load is low, because special moment frame | |
columns with low axial stress are inherently ductile and | |
column yielding at such levels is unlikely to create a column | |
failure mechanism that can lead to collapse. | |
In 18.7.3.2, the nominal strengths of the beams and | |
columns are calculated at the joint faces, and those strengths | |
are compared directly using Eq. (18.7.3.2). The 1995 and | |
earlier Codes required design strengths to be compared at | |
the center of the joint, which typically produced similar | |
results but with added calculation effort. | |
In determining the nominal moment strength of a beam | |
section in negative bending (top in tension), longitudinal | |
reinforcement contained within an effective flange width of a | |
top slab that acts monolithically with the beam increases the | |
beam strength. French and Moehle (1991), on beam-column | |
subassemblies under lateral loading, indicates that using the | |
effective flange widths defined in 6.3.2 gives reasonable | |
estimates of beam negative moment strengths of interior | |
connections at story displacements approaching 2 percent of | |
story height. This effective width is conservative where the | |
slab terminates in a weak spandrel. | |
If 18.7.3.2 cannot be satisfied at a joint, 18.7.3.3 requires | |
that any positive contribution of the column or columns | |
involved to the lateral strength and stiffness of the structure | |
is to be ignored. Negative contributions of the column or | |
columns should not be ignored. For example, ignoring the | |
stiffness of the columns ought not to be used as a justification | |
for reducing the design base shear. If inclusion of those | |
columns in the analytical model of the building results in an | |
increase in torsional effects, the increase should be considered | |
as required by the general building code. Furthermore, | |
the column must be provided with transverse reinforcement | |
to increase its resistance to shear and axial forces. | |
== 18.7.4 Longitudinal reinforcement | |
=== 18.7.4.1 Area of longitudinal reinforcement, Ast, shall be | |
at least 0.01Ag and shall not exceed 0.06Ag. | |
=== 18.7.4.2 In columns with circular hoops, there shall be at | |
least six longitudinal bars. | |
== R18.7.4 Longitudinal reinforcement | |
The lower limit of the area of longitudinal reinforcement | |
is to control time-dependent deformations and to have the | |
yield moment exceed the cracking moment. The upper limit | |
of the area reflects concern for reinforcement congestion, | |
load transfer from floor elements to column (especially in | |
low-rise construction) and the development of high shear | |
stresses. | |
Spalling of the shell concrete, which is likely to occur | |
near the ends of the column in frames of typical configuration, | |
makes lap splices in these locations vulnerable. If lap | |
splices are to be used at all, they should be located near the | |
midheight where stress reversal is likely to be limited to a | |
smaller stress range than at locations near the joints. Transverse | |
reinforcement is required along the lap-splice length ... | |
American Concrete Institute – Copyrighted © Material – www.concrete.org | |
306 ACI 318-19: BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE | |
No further reproduction or distribution is permitted. | |
== R18.7.4 Continuation | |
because of the uncertainty in moment distributions along the | |
height and the need for confinement of lap splices subjected | |
to stress reversals (Sivakumar et al. 1983). | |
=== 18.7.4.3 Over column clear height, longitudinal reinforcement | |
shall be selected such that 1.25ℓd ≤ ℓu/2. | |
=== R18.7.4.3 Bond splitting failure along longitudinal bars | |
within the clear column height may occur under earthquake | |
demands (Ichinose 1995; Sokoli and Ghannoum 2016). | |
Splitting can be controlled by restricting longitudinal bar | |
size, increasing the amount of transverse reinforcement, or | |
increasing concrete strength, all of which reduce the development | |
length of longitudinal bars (ℓd) over column clear | |
height (ℓu). Increasing the ratio of column-to-beam moment | |
strength at joints can reduce the inelastic demands on longitudinal | |
bars in columns under earthquake demands. | |
=== 18.7.4.4 Mechanical splices shall conform to 18.2.7 and | |
welded splices shall conform to 18.2.8. Lap splices shall be | |
permitted only within the center half of the member length, | |
shall be designed as tension lap splices, and shall be enclosed | |
within transverse reinforcement in accordance with 18.7.5.2 | |
and 18.7.5.3. | |
== 18.7.5 Transverse reinforcement | |
=== 18.7.5.1 Transverse reinforcement required in 18.7.5.2 | |
through 18.7.5.4 shall be provided over a length ℓo from each | |
joint face and on both sides of any section where flexural | |
yielding is likely to occur as a result of lateral displacements | |
beyond the elastic range of behavior. Length ℓo shall be at | |
least the greatest of (a) through (c): | |
(a) The depth of the column at the joint face or at the | |
section where flexural yielding is likely to occur | |
(b) One-sixth of the clear span of the column | |
(c) 450 mm | |
=== 18.7.5.2 Transverse reinforcement shall be in accordance | |
with (a) through (f): | |
(a) Transverse reinforcement shall comprise either single | |
or overlapping spirals, circular hoops, or single or overlapping | |
rectilinear hoops with or without crossties. | |
(b) Bends of rectilinear hoops and crossties shall engage | |
peripheral longitudinal reinforcing bars. | |
(c) Crossties of the same or smaller bar size as the hoops | |
shall be permitted, subject to the limitation of 25.7.2.2. | |
Consecutive crossties shall be alternated end for end along | |
the longitudinal reinforcement and around the perimeter | |
of the cross section. | |
(d) Where rectilinear hoops or crossties are used, they | |
shall provide lateral support to longitudinal reinforcement | |
in accordance with 25.7.2.2 and 25.7.2.3. | |
(e) Reinforcement shall be arranged such that the spacing | |
hx of longitudinal bars laterally supported by the corner of | |
a crosstie or hoop leg shall not exceed 350 mm around the | |
perimeter of the column. | |
(f) Where Pu > 0.3Ag fc′ or fc′ > 70 MPa in columns with | |
rectilinear hoops, every longitudinal bar or bundle of bars | |
around the perimeter of the column core shall have lateral | |
support provided by the corner of a hoop or by a seismic | |
hook, and the value of hx shall not exceed 200 mm. Pu | |
shall be the largest value in compression consistent with | |
factored load combinations including E. | |
== R18.7.5 Transverse reinforcement | |
This section is concerned with confining the concrete and | |
providing lateral support to the longitudinal reinforcement. | |
=== R18.7.5.1 This section stipulates a minimum length over | |
which to provide closely-spaced transverse reinforcement at | |
the column ends, where flexural yielding normally occurs. | |
Research results indicate that the length should be increased | |
by 50 percent or more in locations, such as the base of a | |
building, where axial loads and flexural demands may be | |
especially high (Watson et al. 1994). | |
=== R18.7.5.2 Sections 18.7.5.2 and 18.7.5.3 provide requirements | |
for configuration of transverse reinforcement for | |
columns and joints of special moment frames. Figure | |
=== R18.7.5.2 shows an example of transverse reinforcement | |
provided by one hoop and three crossties. Crossties with | |
a 90-degree hook are not as effective as either crossties | |
with 135-degree hooks or hoops in providing confinement. | |
For lower values of Pu/Ag fc′ and lower concrete compressive | |
strengths, crossties with 90-degree hooks are adequate | |
if the ends are alternated along the length and around the | |
perimeter of the column. For higher values of Pu/Ag fc′, for | |
which compression-controlled behavior is expected, and for | |
higher compressive strengths, for which behavior tends to be | |
more brittle, the improved confinement provided by having | |
corners of hoops or seismic hooks supporting all longitu- ... | |
American Concrete Institute – Copyrighted © Material – www.concrete.org | |
PART 5: EARTHQUAKE RESISTANCE 307 | |
18 Seismic | |
No further reproduction or distribution is permitted. | |
=== R18.7.5.2 Continuation | |
dinal bars is important to achieving intended performance. | |
Where these conditions apply, crossties with seismic hooks | |
at both ends are required. The 200 mm limit on hx is also | |
intended to improve performance under these critical conditions. | |
For bundled bars, bends or hooks of hoops and crossties | |
need to enclose the bundle, and longer extensions on | |
hooks should be considered. Column axial load Pu should | |
reflect factored compressive demands from both earthquake | |
and gravity loads. | |
In past editions of the Code, the requirements for transverse | |
reinforcement in columns, walls, beam-column joints, and | |
diagonally reinforced coupling beams referred to the same | |
equations. In the 2014 edition of the Code, the equations and | |
detailing requirements differ among the member types based | |
on consideration of their loadings, deformations, and performance | |
requirements. Additionally, hx previously referred to | |
the distance between legs of hoops or crossties. In the 2014 | |
edition of the Code, hx refers to the distance between longitudinal | |
bars supported by those hoops or crossties. | |
Fig. R18.7.5.2—Example of transverse reinforcement in | |
columns. | |
=== 18.7.5.3 Spacing of transverse reinforcement shall not | |
exceed the least of (a) through (d): | |
(a) One-fourth of the minimum column dimension | |
(b) For Grade 420, 6db of the smallest longitudinal bar | |
(c) For Grade 550, 5db of the smallest longitudinal bar | |
(d) so, as calculated by: | |
| |
so = 100 + ( (350-hx)/3 ) | |
(18.7.5.3) | |
| |
The value of so from Eq. (18.7.5.3) shall not exceed 150 | |
mm and need not be taken less than 100 mm. | |
=== 18.7.5.4 Amount of transverse reinforcement shall be in | |
accordance with Table 18.7.5.4 . | |
The concrete strength factor kf and confinement effectiveness | |
factor kn are calculated according to Eq. (18.7.5.4a) and | |
(18.7.5.4b). | |
| |
(a) kf = fc'/175 + 0.6 >= 1.0; (18.7.5.4a) | |
| |
(b) kn = nl / (nl - 2); (18.7.5.4b) | |
| |
where nl is the number of longitudinal bars or bar bundles | |
around the perimeter of a column core with rectilinear hoops | |
that are laterally supported by the corner of hoops or by | |
seismic hooks. | |
Table 18.7.5.4—Transverse reinforcement for | |
columns of special moment frames_ | |
=== R18.7.5.3 The requirement that spacing not exceed onefourth | |
of the minimum member dimension or 150 mm is for | |
concrete confinement. If the maximum spacing of crossties or | |
legs of overlapping hoops within the section is less than 350 | |
mm, then the 100 mm limit can be increased as permitted by | |
Eq. (18.7.5.3). The spacing limit as a function of the longitudinal | |
bar diameter is intended to provide adequate longitudinal | |
bar restraint to control buckling after spalling. | |
American Concrete Institute – Copyrighted © Material – www.concrete.org | |
308 ACI 318-19: BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE | |
No further reproduction or distribution is permitted. | |
=== R18.7.5.4 The effect of helical (spiral) reinforcement and | |
adequately configured rectilinear hoop reinforcement on | |
deformation capacity of columns is well established (Sakai | |
and Sheikh 1989). Expressions (a), (b), (d), and (e) in | |
Table 18.7.5.4 have historically been used in ACI 318 to calculate | |
the required confinement reinforcement to ensure that | |
spalling of shell concrete does not result in a loss of column | |
axial load strength. Expressions (c) and (f) were developed | |
from a review of column test data (Elwood et al. 2009) and | |
are intended to result in columns capable of sustaining a drift | |
ratio of 0.03 with limited strength degradation. Expressions | |
(c) and (f) are triggered for axial load greater than 0.3Ag fc′, | |
which corresponds approximately to the onset of compression- | |
controlled behavior for symmetrically reinforced | |
columns. The kn term (Paultre and Légeron 2008) decreases | |
the required confinement for columns with closely spaced, | |
laterally supported longitudinal reinforcement because such | |
columns are more effectively confined than columns with | |
more widely spaced longitudinal reinforcement. The kf term | |
increases the required confinement for columns with fc′ > 70 | |
MPa because such columns can experience brittle failure if | |
not well confined. Concrete strengths greater than 100 MPa | |
should be used with caution given the limited test data for | |
such columns. The concrete strength used to determine the | |
confinement reinforcement is required to be the same as that | |
specified in the construction documents. | |
Expressions (a), (b), and (c) in Table 18.7.5.4 are to be | |
satisfied in both cross-sectional directions of the rectangular | |
core. For each direction, bc is the core dimension perpendicular | |
to the tie legs that constitute Ash, as shown in Fig. R18.7.5.2 . | |
Research results indicate that high strength reinforcement | |
can be used effectively as confinement reinforcement. | |
Section 20.2.2.4 permits a value of fyt as high as 690 MPa to | |
be used in Table 18.7.5.4. | |
=== 18.7.5.5 Beyond the length ℓo given in 18.7.5.1, the column | |
shall contain spiral reinforcement satisfying 25.7.3 or hoop | |
and crosstie reinforcement satisfying 25.7.2 and 25.7.4 with | |
spacing s not exceeding the least of 150 mm, 6db of the smallest | |
Grade 420 longitudinal column bar, and 5db of the smallest | |
Grade 550 longitudinal column bar, unless a greater amount | |
of transverse reinforcement is required by 18.7.4.4 or 18.7.6. | |
=== R18.7.5.5 This provision is intended to provide reasonable | |
protection to the midheight of columns outside the length | |
ℓo. Observations after earthquakes have shown significant | |
damage to columns in this region, and the minimum hoops | |
or spirals required should provide more uniform strength of | |
the column along its length. | |
American Concrete Institute – Copyrighted © Material – www.concrete.org | |
PART 5: EARTHQUAKE RESISTANCE 309 | |
18 Seismic | |
No further reproduction or distribution is permitted. | |
=== 18.7.5.6 Columns supporting reactions from discontinued | |
stiff members, such as walls, shall satisfy (a) and (b): | |
(a) Transverse reinforcement required by 18.7.5.2 through | |
18.7.5.4 shall be provided over the full height at all levels | |
beneath the discontinuity if the factored axial compressive | |
force in these columns, related to earthquake effect, | |
exceeds Ag fc′/10. Where design forces have been magnified | |
to account for the overstrength of the vertical elements | |
of the seismic-force-resisting system, the limit of Ag fc′/10 | |
shall be increased to Ag fc′/4. | |
(b) Transverse reinforcement shall extend into the discontinued | |
member at least ℓd of the largest longitudinal | |
column bar, where ℓd is in accordance with 18.8.5. Where | |
the lower end of the column terminates on a wall, the | |
required transverse reinforcement shall extend into the | |
wall at least ℓd of the largest longitudinal column bar at the | |
point of termination. Where the column terminates on a | |
footing or mat, the required transverse reinforcement shall | |
extend at least 300 mm into the footing or mat. | |
=== R18.7.5.6 Columns supporting discontinued stiff | |
members, such as walls or trusses, may develop considerable | |
inelastic response. Therefore, it is required that these ... | |
columns have the specified reinforcement throughout their | |
length. This covers all columns beneath the level at which | |
the stiff member has been discontinued, unless the factored | |
forces corresponding to earthquake effect are low. Refer to | |
R18.12.7.6 for discussion of the overstrength factor Ωo. | |
=== 18.7.5.7 If the concrete cover outside the confining transverse | |
reinforcement required by 18.7.5.1, 18.7.5.5, and | |
18.7.5.6 exceeds 100 mm, additional transverse reinforcement | |
having cover not exceeding 100 mm and spacing not | |
exceeding 300 mm shall be provided. | |
=== R18.7.5.7 The unreinforced shell may spall as the column | |
deforms to resist earthquake effects. Separation of portions | |
of the shell from the core caused by local spalling creates a | |
falling hazard. The additional reinforcement is required to | |
reduce the risk of portions of the shell falling away from the | |
column. | |
== 18.7.6 Shear strength | |
=== 18.7.6.1 Design forces | |
==== 18.7.6.1.1 The design shear force Ve shall be calculated | |
from considering the maximum forces that can be generated | |
at the faces of the joints at each end of the column. These | |
joint forces shall be calculated using the maximum probable | |
flexural strengths, Mpr, at each end of the column associated | |
with the range of factored axial forces, Pu, acting on the | |
column. The column shears need not exceed those calculated | |
from joint strengths based on Mpr of the beams framing into | |
the joint. In no case shall Ve be less than the factored shear | |
calculated by analysis of the structure. | |
=== 18.7.6.2 Transverse reinforcement | |
==== 18.7.6.2.1 Transverse reinforcement over the lengths ℓo, | |
given in 18.7.5.1, shall be designed to resist shear assuming | |
Vc = 0 when both (a) and (b) occur: | |
(a) The earthquake-induced shear force, calculated in | |
accordance with 18.7.6.1, is at least one-half of the | |
maximum required shear strength within ℓo. | |
(b) The factored axial compressive force Pu including | |
earthquake effects is less than Ag fc′/20. | |
== R18.7.6 Shear strength | |
=== R18.7.6.1 Design forces | |
==== R18.7.6.1.1 The procedures of 18.6.5.1 also apply to | |
columns. Above the ground floor, the moment at a joint may | |
be limited by the flexural strength of the beams framing | |
into the joint. Where beams frame into opposite sides of | |
a joint, the combined strength is the sum of the negative | |
moment strength of the beam on one side of the joint and | |
the positive moment strength of the beam on the other side | |
of the joint. Moment strengths are to be determined using a | |
strength reduction factor of 1.0 and reinforcement with an | |
effective yield stress equal to at least 1.25fy. Distribution of | |
the combined moment strength of the beams to the columns | |
above and below the joint should be based on analysis. | |
American Concrete Institute – Copyrighted © Material – www.concrete.org | |
310 ACI 318-19: BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE | |
No further reproduction or distribution is permitted. | |
[ Lanjut Ke 18.8—Joints of special moment frames ... ] | |
| |
| |