= 18. CHAPTER 18 — EARTHQUAKE-RESISTANT STRUCTURES

= 18.6 — Beams of special moment frames

== 18.6.1 Scope

=== 18.6.1.1 This section shall apply to beams of special moment
frames that form part of the seismic-force-resisting system and
are proportioned primarily to resist flexure and shear.

=== 18.6.1.2 Beams of special moment frames shall frame into
columns of special moment frames satisfying 18.7.

= R18.6 — Beams of special moment frames

== R18.6.1 Scope
 This section applies to beams of special moment frames
resisting lateral loads induced by earthquake motions. In
previous Codes, any frame member subjected to a factored
axial compressive force exceeding (Ag fc′/10) under any
load combination was to be proportioned and detailed as
described in 18.7. In the 2014 Code, all requirements for
beams are contained in 18.6 regardless of the magnitude of
axial compressive force.
 This Code is written with the assumption that special
moment frames comprise horizontal beams and vertical
columns interconnected by beam-column joints. It is acceptable
for beams and columns to be inclined provided the
resulting system behaves as a frame—that is, lateral resistance
is provided primarily by moment transfer between
beams and columns rather than by strut or brace action. In
special moment frames, it is acceptable to design beams to
resist combined moment and axial force as occurs in beams
that act both as moment frame members and as chords or
collectors of a diaphragm. It is acceptable for beams of
special moment frames to cantilever beyond columns, but
such cantilevers are not part of the special moment frame
that forms part of the seismic-force-resisting system. It is
acceptable for beams of a special moment frame to connect
into a wall boundary if the boundary is reinforced as a
special moment frame column in accordance with 18.7.
A concrete braced frame, in which lateral resistance is
provided primarily by axial forces in beams and columns, is
not a recognized seismic-force-resisting system.
American Concrete Institute – Copyrighted © Material – www.concrete.org
PART 5: EARTHQUAKE RESISTANCE 299
18 Seismic
No further reproduction or distribution is permitted.

== 18.6.2 Dimensional limits

=== 18.6.2.1 Beams shall satisfy (a) through (c):
(a) Clear span ℓn shall be at least 4d
(b) Width bw shall be at least the lesser of 0.3h and 250 mm
(c) Projection of the beam width beyond the width of the
supporting column on each side shall not exceed the lesser
of c2 and 0.75c1.

== R18.6.2 Dimensional limits
 Experimental evidence (Hirosawa 1977) indicates that,
under reversals of displacement into the nonlinear range,
behavior of continuous members having length-to-depth
ratios of less than 4 is significantly different from the behavior
of relatively slender members. Design rules derived from
experience with relatively slender members do not apply
directly to members with length-to-depth ratios less than 4,
especially with respect to shear strength.
 Geometric constraints indicated in 18.6.2.1(b) and (c) were
derived from practice and research (ACI 352R) on reinforced
concrete frames resisting earthquake-induced forces. The limits
in 18.6.2.1(c) define the maximum beam width that can effectively
transfer forces into the beam-column joint. An example
of maximum effective beam width is shown in Fig. R18.6.2.

Fig. R18.6.2 — Maximum effective width of wide beam and
required transverse reinforcement.
American Concrete Institute – Copyrighted © Material – www.concrete.org
300 ACI 318-19: BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
No further reproduction or distribution is permitted.

== 18.6.3 Longitudinal reinforcement

=== 18.6.3.1 Beams shall have at least two continuous bars at
both top and bottom faces. At any section, for top as well as
for bottom reinforcement, the amount of reinforcement shall
be at least that required by 9.6.1.2, and the reinforcement
ratio ρ shall not exceed 0.025 for Grade 420 reinforcement
and 0.02 for Grade 550 reinforcement.

=== 18.6.3.2 Positive moment strength at joint face shall be at
least one-half the negative moment strength provided at that
face of the joint. Both the negative and the positive moment
strength at any section along member length shall be at least
one-fourth the maximum moment strength provided at face
of either joint.

=== 18.6.3.3 Lap splices of deformed longitudinal reinforcement
shall be permitted if hoop or spiral reinforcement is
provided over the lap length. Spacing of the transverse reinforcement
enclosing the lap-spliced bars shall not exceed the
lesser of d/4 and 100 mm. Lap splices shall not be used in
locations (a) through (c):
(a) Within the joints
(b) Within a distance of twice the beam depth from the
face of the joint;
(c) Within a distance of twice the beam depth from critical
sections where flexural yielding is likely to occur as
a result of lateral displacements beyond the elastic range
of behavior;

=== 18.6.3.4 Mechanical splices shall conform to 18.2.7 and
welded splices shall conform to 18.2.8.

=== 18.6.3.5 Unless used in a special moment frame as permitted
by 18.9.2.3, prestressing shall satisfy (a) through (d):
(a) The average prestress fpc calculated for an area equal to
the least cross-sectional dimension of the beam multiplied
by the perpendicular cross-sectional dimension shall not
exceed the lesser of 3.5 MPa and fc′/10.
(b) Prestressed reinforcement shall be unbonded in potential
plastic hinge regions, and the calculated strains in
prestressed reinforcement under the design displacement
shall be less than 0.01.
(c) Prestressed reinforcement shall not contribute more
than one-fourth of the positive or negative flexural strength
at the critical section in a plastic hinge region and shall be
anchored at or beyond the exterior face of the joint.
(d) Anchorages of post-tensioning tendons resisting earthquake-
induced forces shall be capable of allowing tendons
to withstand 50 cycles of loading, with prestressed reinforcement
forces bounded by 40 and 85 percent of the
specified tensile strength of the prestressing reinforcement.

== R18.6.3 Longitudinal reinforcement

=== R18.6.3.1 The limiting reinforcement ratios of 0.025 and
0.02 are based primarily on considerations of providing
adequate deformation capacity, avoiding reinforcement
congestion, and, indirectly, on limiting shear stresses in
beams of typical proportions.

=== R18.6.3.3 Lap splices of reinforcement are prohibited
along lengths where flexural yielding is anticipated because
such splices are not reliable under conditions of cyclic
loading into the inelastic range. Transverse reinforcement
for lap splices at any location is mandatory because of the
potential of concrete cover spalling and the need to confine
the splice.

=== R18.6.3.5 These provisions were developed, in part, based
on observations of building performance in earthquakes
(ACI 423.3R). For calculating the average prestress, the least
cross-sectional dimension in a beam normally is the web
dimension, and is not intended to refer to the flange thickness.
In a potential plastic hinge region, the limitation on
strain and the requirement for unbonded tendons are intended
to prevent fracture of tendons under inelastic earthquake
deformation. Calculation of strain in the prestressed reinforcement
is required considering the anticipated inelastic
mechanism of the structure. For prestressed reinforcement
unbonded along the full beam span, strains generally will
be well below the specified limit. For prestressed reinforcement
with short unbonded length through or adjacent to the
joint, the additional strain due to earthquake deformation is
calculated as the product of the depth to the neutral axis and
the sum of plastic hinge rotations at the joint, divided by the
unbonded length.
 The restrictions on the flexural strength provided by the
tendons are based on the results of analytical and experimental
studies (Ishizuka and Hawkins 1987; Park and
American Concrete Institute – Copyrighted © Material – www.concrete.org
PART 5: EARTHQUAKE RESISTANCE 301
18 Seismic
No further reproduction or distribution is permitted.

=== R18.6.3.5 Continuation
Thompson 1977). Although satisfactory seismic performance
can be obtained with greater amounts of prestressed
reinforcement, this restriction is needed to allow the use of
the same response modification and deflection amplification
factors as those specified in model codes for special moment
frames without prestressed reinforcement. Prestressed
special moment frames will generally contain continuous
prestressed reinforcement that is anchored with adequate
cover at or beyond the exterior face of each beam-column
connection located at the ends of the moment frame.
 Fatigue testing for 50 cycles of loading between 40 and
80 percent of the specified tensile strength of the prestressed
reinforcement has been a long-standing industry practice
(ACI 423.3R; ACI 423.7). The 80 percent limit was
increased to 85 percent to correspond to the 1 percent limit
on the strain in prestressed reinforcement. Testing over this
range of stress is intended to conservatively simulate the
effect of a severe earthquake. Additional details on testing
procedures are provided in ACI 423.7.

== 18.6.4 Transverse reinforcement

=== 18.6.4.1 Hoops shall be provided in the following regions
of a beam:
(a) Over a length equal to twice the beam depth measured
from the face of the supporting column toward midspan,
at both ends of the beam;
(b) Over lengths equal to twice the beam depth on both
sides of a section where flexural yielding is likely to occur
as a result of lateral displacements beyond the elastic
range of behavior.

=== 18.6.4.2 Where hoops are required, primary longitudinal
reinforcing bars closest to the tension and compression faces
shall have lateral support in accordance with 25.7.2.3 and
25.7.2.4. The spacing of transversely supported flexural
reinforcing bars shall not exceed 350 mm. Skin reinforcement
required by 9.7.2.3 need not be laterally supported.

=== 18.6.4.3 Hoops in beams shall be permitted to be made
up of two pieces of reinforcement: a stirrup having seismic
hooks at both ends and closed by a crosstie. Consecutive
crossties engaging the same longitudinal bar shall have their
90-degree hooks at opposite sides of the flexural member.
If the longitudinal reinforcing bars secured by the crossties
are confined by a slab on only one side of the beam, the
90-degree hooks of the crossties shall be placed on that side.

=== 18.6.4.4 The first hoop shall be located not more than 50
mm from the face of a supporting column. Spacing of the
hoops shall not exceed the least of (a) through (d):
(a) d/4
(b) 150 mm
(c) For Grade 420, 6db of the smallest primary flexural
reinforcing bar excluding longitudinal skin reinforcement
required by 9.7.2.3
(d) For Grade 550, 5db of the smallest primary flexural
reinforcing bar excluding longitudinal skin reinforcement
required by 9.7.2.3

== R18.6.4 Transverse reinforcement
 Transverse reinforcement is required primarily to confine
the concrete and maintain lateral support for the reinforcing
bars in regions where yielding is expected. Examples of
hoops suitable for beams are shown in Fig. R18.6.4.
 In earlier Code editions, the upper limit on hoop spacing
was the least of d/4, eight longitudinal bar diameters, 24 tie
bar diameters, and 300 mm. The upper limits were changed in
the 2011 edition because of concerns about adequacy of longitudinal
bar buckling restraint and confinement in large beams.
 In the case of members with varying strength along the
span or members for which the permanent load represents a
large proportion of the total design load, concentrations of
inelastic rotation may occur within the span. If such a condition
is anticipated, transverse reinforcement is also required
in regions where yielding is expected. Because spalling of
the concrete shell might occur, especially at and near regions
of flexural yielding, all web reinforcement is required to be
provided in the form of closed hoops.
American Concrete Institute – Copyrighted © Material – www.concrete.org
302 ACI 318-19: BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
No further reproduction or distribution is permitted.

=== 18.6.4.5 Where hoops are required, they shall be designed
to resist shear according to 18.6.5.

=== 18.6.4.6 Where hoops are not required, stirrups with
seismic hooks at both ends shall be spaced at a distance not
more than d/2 throughout the length of the beam.

=== 18.6.4.7 In beams having factored axial compressive
force exceeding Ag fc′/10, hoops satisfying 18.7.5.2 through
18.7.5.4 shall be provided along lengths given in 18.6.4.1.
Along the remaining length, hoops satisfying 18.7.5.2 shall
have spacing s not exceeding the least of 150 mm, 6db of the
smallest Grade 420 enclosed longitudinal beam bar, and 5db
of the smallest Grade 550 enclosed longitudinal beam bar.
Where concrete cover over transverse reinforcement exceeds
100 mm, additional transverse reinforcement having cover
not exceeding 100 mm and spacing not exceeding 300 mm
shall be provided.

Fig. R18.6.4 — Examples of overlapping hoops and illustration
of limit on maximum horizontal spacing of supported
longitudinal bars.

== 18.6.5 Shear strength

=== 18.6.5.1 Design forces
 The design shear force Ve shall be calculated from consideration
of the forces on the portion of the beam between faces
of the joints. It shall be assumed that moments of opposite
sign corresponding to probable flexural strength, Mpr, act at
the joint faces and that the beam is loaded with the factored
gravity and vertical earthquake loads along its span.

=== 18.6.5.2 Transverse reinforcement
 Transverse reinforcement over the lengths identified in
18.6.4.1 shall be designed to resist shear assuming Vc = 0
when both (a) and (b) occur:
(a) The earthquake-induced shear force calculated in
accordance with 18.6.5.1 represents at least one-half of
the maximum required shear strength within those lengths.
(b) The factored axial compressive force Pu including
earthquake effects is less than Ag fc′/20.

== R18.6.5 Shear strength
 Unless a beam possesses a moment strength that is on
the order of 3 or 4 times the design moment, it should be
assumed that it will yield in flexure in the event of a major
earthquake. The design shear force should be selected so as
to be a good approximation of the maximum shear that may
develop in a member. Therefore, required shear strength
for frame members is related to flexural strengths of the
designed member rather than to factored shear forces indicated
by lateral load analysis. The conditions described by
18.6.5.1 are illustrated in Fig. R18.6.5. The figure also shows
that vertical earthquake effects are to be included, as is typically
required by the general building code. For example,
ASCE/SEI 7 requires vertical earthquake effects, 0.2SDS, to
be included.
 Because the actual yield strength of the longitudinal
reinforcement may exceed the specified yield strength and
because strain hardening of the reinforcement is likely to
American Concrete Institute – Copyrighted © Material – www.concrete.org
PART 5: EARTHQUAKE RESISTANCE 303
18 Seismic
No further reproduction or distribution is permitted.

== R18.6.5 Continuation
take place at a joint subjected to large rotations, required
shear strengths are determined using a stress of at least
1.25fy in the longitudinal reinforcement.
 Experimental studies (Popov et al. 1972) of reinforced
concrete members subjected to cyclic loading have demonstrated
that more shear reinforcement is required to ensure
a flexural failure if the member is subjected to alternating
nonlinear displacements than if the member is loaded in only
one direction: the necessary increase of shear reinforcement
being higher in the case of no axial load. This observation
is reflected in the Code (refer to 18.6.5.2) by eliminating
the term representing the contribution of concrete to shear
strength. The added conservatism on shear is deemed necessary
in locations where potential flexural hinging may occur.
However, this stratagem, chosen for its relative simplicity,
should not be interpreted to mean that no concrete is
required to resist shear. On the contrary, it may be argued
that the concrete core resists all the shear with the shear
(transverse) reinforcement confining and strengthening the
concrete. The confined concrete core plays an important
role in the behavior of the beam and should not be reduced
to a minimum just because the design expression does not
explicitly recognize it.
American Concrete Institute – Copyrighted © Material – www.concrete.org
304 ACI 318-19: BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE
No further reproduction or distribution is permitted.

Fig. R18.6.5 — Design shears for beams and columns.
American Concrete Institute – Copyrighted © Material – www.concrete.org
PART 5: EARTHQUAKE RESISTANCE 305
18 Seismic
No further reproduction or distribution is permitted.


[ Lanjut Ke 18.7—Columns of special moment frames ... ]






Back To Contents